  • XTH2 Transmitter comes with installation screw kit
  • Ambient Temperature: -40 to 185°F (-40 to 85°C)
  • Област за инсталација:
    Field housing; connection head Form B according to DIN 43729
  • Installation angle: No limit
    Забелешка: Max. mounting screw torque: 3/4 lb·ft (1 N·m)

AutomationDirect XTD2 0100F J Temperature Transmitter - housing

Димензии

mm [инчи]

AutomationDirect XTD2 0100F J Temperature Transmitter - Dimensions

Head transmitter type with screw terminals.
A – Spring travel L ≥ 5 mm
B – Mounting elements for attachable measured value display
Screw terminals – 24.1 mm (0.95 in)
Installation of DIN Rail transmitter

AutomationDirect XTD2 0100F J Temperature Transmitter - DIN

Mount the device vertically and ensure it is correctly oriented.

  1. Slide the device top DIN rail groove onto the top of the DIN rail.
  2. Rotate the device into the bottom of the DIN rail, until you can hear the DIN rail clip click into place on the DIN rail edge.
  3. Pull gently on the device to check secure mounting on the DIN rail.

mm [инчи]

AutomationDirect XTD2 0100F J Temperature Transmitter - DIN 1

DIN Rail transmitter with screw terminals.

  • Operating Ambient Temperature Range: -40 to 185°F (-40 to 85°C)
  • Installation angle: No limit

Wiring Head Type

AutomationDirect XTD2 0100F J Temperature Transmitter - Transmitter

Инструкции за безбедност:

  • To comply with UL61010-1 unit must be supplied by class 2 power supply.
  • Disconnect power before making connections.

AutomationDirect XTD2 0100F J Temperature Transmitter - Load Impedance

Заштитување
Please take note: When installing the head style transmitter remotely from the sensor in a field housing, the shield on the 4-20 mA signal output must have the same potential as the shield at the sensor connections. When using grounded thermocouples, shielding of the output 4-20 mA cable is recommended. In facilities with strong electromagnetic fields, shielding of all cables with a low Ohm connection to the transmitter housing is recommended.
Due to the danger of lightning strikes it is recommended that shielded cable be used in outdoor installations.
Wiring DIN Type

AutomationDirect XTD2 0100F J Temperature Transmitter - Load Impedance 1

Инструкции за безбедност:

  • To comply with UL61010-1 unit must be supplied by class 2 power supply.
  • Disconnect power before making connections.

Импеданса на оптоварување

AutomationDirect XTD2 0100F J Temperature Transmitter - output

Заштитување
The shield on the 4-20 mA signal output cable must have the same potential as the shield at the sensor connections. When using grounded thermocouples, shielding of the output 4-20 mA cable is recommended. In facilities with strong electromagnetic fields, shielding of all cables with a low Ohm connection to the transmitter housing is recommended.
Due to the danger of lightning strikes it is recommended that shielded cable be used in outdoor installations.

Ве молиме посетете www.automationdirect.com for specifications and additional information.AutomationDirect XTD2 0100F J Temperature Transmitter - Bar Code