Cannex Technology F-101 Wireless Remote Controller

F-101 Temperature Controller Panel Specifications
- Димензии: 16.5 × 5 × 1.4 cm
- Set Temp Range : 15°C–35°C (59°F–95°F)
- Timer Range : 1–24 hours (display hidden when set to 0 hour)
- Infrared Effective Linear Distance : 6–8 m (varies slightly by environment)
- Functions : → Cool (Cooling) / Hot (Heating) / Fan (Ventilation) Cool (Cooling) / De-wet (Dehumidification) / Fan (Ventilation)
- °C/°F Switching : Toggle via the internal circuit board (backside of remote) or Hold both Temp +/- buttons simultaneously for 10 seconds after power-on.
- Modes : Cooling-only / Heat-Cool / Direct Expansion (low current, high current, 25A)
- Wire-Free Connection : Between control box and remote.
Ф-101
Безжичен далечински управувач
F-101 Remote Controller Operation Guide
- Initial Battery Installation (RESET State)
When batteries are installed for the first time, all LCD segments will illuminate for 5 seconds to verify display functionality. - Operation Mode → Cooling (Cool)
- Set Temperature → 26°C
- Fan Speed → Auto
- Sleep Function → Off
- Airflow Direction → Not supported (for chiller unit models)
- Timer Function → Disabled (0 hour)
Избор на режим на работа
- Press the “Mode” button to cycle through modes
Cooling (Cool) Fan (Ventilation) Heating (Hot) - Temperature Setting (SET TEMP) :
- In Cooling (Cool) Mode
Press ▲/▼ to adjust temperature (range : 15°C–35 °C). - In Hot Mode
Press ▲/▼ to adjust temperature (15°C–35°C) - In Fan mode
Temperature control is disabled (host relay remains OFF)
Поставување брзина на вентилаторот
- Press the “Fan Speed” button to cycle through :
High (HI)、Medium (MED)、Low (LO)、Auto (AUTO) - Sleep Function (SLEEP) :
- For use during sleep
- In Cool / Heat mode
- Press again to cancel Sleep function
- Air Direction Setting (OSC.) :
Not available (for chiller unit models) (Covered by nameplate) - Setting Auto-Off Timer (TIMER) :
While unit is ON :
Press “Timer” button (▲/▼) to set desired OFF time - Setting Auto-On Timer (TIMER) :
While unit is OFF : Press “Timer” button (▲/▼) to set desired ON time - Power On / Off (POWER On / Off) :
- Press “Operation / Stop” button to turn ON
- Press again while ON to turn OFF
- When powered ON, host RELAY→On
Статус на светлото на индикаторот на ресиверот
- Power-on confirmation → Blue light flashes 3 times & green light stays on (turns off after 5 seconds)
- Blue light stays on → Water valve On during operation
- Blue light slow flash (10s off / 0.4s on) → Water valve Off during operation (serves as power indicator)
- Blue light fast flash → Abnormal status
- Green light → Comfort sleep mode
- Red light → Scheduled power on/off
- Orange light → Sleep mode + scheduled power off
- Upon receiving signal from remote controller → Buzzer sounds once briefly
Забелешка
- Red indicates correction point
- The built-in temperature sensor in this receiver must be installed near the return air vent or in a well-ventilated area.
Air Conditioning Functions
Режим на ладење
- Three-way Valve Operation
- Room temperature ≥ Set temperature → Three-way valve On
- Room temperature ≤ (Set temperature -1°C) → Thr ee-way valve Off
- Three-way valve has 1-minute delay start protection
Операција на вентилаторот
Manual Fan Mode : 3-speed adjustment (High/Medium/Low)
Auto Fan Mode in Cooling
- Room temperature ≤ Set temperature → Low
- Set temperature < Room temperature < (Set temperature +4°C) → Medium
- Room temperature ≥ (Set temperature +4°C) → High
Режим на греење
Three-way Valve Operation
- Room temperature ≤ Set temperature → Three-way valve On
- Room temperature ≥ Set temperature +1°C → Three-way valve Off
- Three-way valve has 1-minute delay start protection
- Операција на вентилаторот
Manual Fan Mode : 3-speed adjustment (High/Medium/Low)
Auto Fan Mode in Heating
- Set temperature ≤ Room temperature → Low
- Room temperature < Set temperature < Room tempe rature +4°C → Medium
- Set temperature ≥ Room temperature +4°C → High
Проширени модели
- Direct Expansion Air Conditioner Special Type (Additional Functions) :
- Three-way valve has 3-minute delay start protection (Can be equipped with high-current RELAY for compressor control)
- Air direction louver (OSC.) setting : Controls main unit RELAY → ON/OFF as air direction louver function